Modem - Settings; Rs232 - Settings; Tc57 - Settings - Siemens SIPROTEC 4 Manual

Remote control via ethernet-modems 7xv585x and 7xv5655
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Modem - Settings

In this window only the field "local Echo on (E1) must
(may) be checked.

RS232 - Settings

In the window "RS232" the RS232-interface
parameters are set.
The office modem should in general be set to
Baudrate 57600 Databits 8 Parity No Stop (Bits) 1
The other basic settings
TotalReadTimeout, CharDistance,
Should not be changed.

TC57 - Settings

For communication with DIGSI- or IEC60870-5-1 protocol, the protocol detection TC57 should be
activated. This is however unnecessary here, as the settings made here are re-set in the office
modem before each dial-up process. The corresponding entry is made in DIGSI 4.
Save all settings with OK and close the window.
HELP_DIG4_SIP4_ETHERNET_A2.DOC
Seite 13 von 21