6000 SERIES HUB INSTALLATION

LOCATION

1. Mount the 6000 Series Hub near the HVAC equipment, on an
interior wall, stud or return duct. See FIGURE 2.
2. Locate the Discharge Air Temperature (DAT) in the supply trunk,
downstream of the heat exchanger and cooling coils, and before
the zone dampers (refer to the shaded areas of FIGURE 2).
Note: Do not mount the sensor in direct line-of-sight of the heat
exchanger, cooling coils or UV lights as this may cause the sensor
to report false temperature readings. Do not route wires along
120VAC lines.
3. Before wiring the sensor to the 6000 Series Hub, measure
the resistance across the sensor. The resistance corresponds
(approximately) to the sensed temperature according to TABLE 1.
TABLE 1 – DAT SENSOR RESISTANCE
Temperature (°F)
30
40
Resistance (k )
34.6
26.1

MOUNTING

1. Separate the 6000 Series Hub cover from the base. See FIGURE 3.
2. Use the base as a template to drill mounting holes. See FIGURE 4 for mounting hole locations.
3. Attach the base to an interior wall, stud or return duct.
FIGURE 3
2
1
90-2408
50
60
70
80
90
19.9
15.3
11.9
9.4
7.4
FIGURE 4 – 6000 SERIES HUB MOUNTING LOCATION
USE TWO SCREWS WHEN
ATTACHING TO A WALL STUD
FIGURE 2 – 6000 SERIES HUB MOUNTING LOCATION
LOCATE DAT
SENSOR IN
SHADED AREA
(SUPPLY DUCT)
100
5.9
90-2407
HUB MOUNTED ON
WALL OR STUD
HUB MOUNTED ON
RETURN DUCT
USE FOUR SCREWS
WHEN ATTACHING TO
DRYWALL/PLASTER
90-2409
7