INSTALLER SETUP
6000 SERIES CONTROL
The 6000 Series Hub is powered by 24VAC. The 6000 Series Control is powered by the 6000 Series Hub. In the case of power loss, the system will
maintain the clock for 24 hours. The system has a memory backup that saves the system settings in case of power interruption. The factory reset is
located in the Installer Tools option of the Installer Menu. See Installer System Settings section for details.
INSTALLER SETUP MENU
The first time the system is powered up (or after
a factory reset) it will enter the Installer Setup
Menu. All installer settings can be set here. The
installer settings are also accessible in the MENU
by pressing the Contractor Info button for 10
seconds. Installer settings can be imported and
exported via USB drive. This feature can be
found by selecting the Installer Tools button on
the Installer Settings Menu Screen.
INSTALLER TOOLS AND TEST TABLE
TABLE 2: INSTALLER TOOLS AND TEST MENU
Function
Import USB Settings
Export USB Settings
Factory Reset
Connection Type
Installer Test
INSTALLER SETTINGS TABLES
The following tables contain the system settings and their details. Default settings are shown in bold. The availability of some settings is dependent
upon the value of other settings.
TABLE 3: GENERAL SYSTEM SETTINGS
System Setting
Installer Temperature Scale
Contractor Information Input
Description
Import installer settings from another 6000 Series Control. USB drive required.
Export installer settings to use on another 6000 Series Control. USB drive required.
Reset the control back to factory defaults.
Select whether the control will connect to the Aprilaire App (default) or to an home automation system.
Test equipment outputs. See page 23.
Description
This selection only effects the installer setup menus.
Enter contractor's contact information.
Factory Default Settings (bold)
and Settings Range
Fahrenheit
Celsius
Company, Phone, Email, Web.
15