TABLE 4: THERMOSTAT SYSTEM SETTINGS
System Setting
RH Sensor Offset Zone 1
Temp Sensor Offset Zone 2
RH Sensor Offset Zone 2
Temp Sensor Offset Zone 3
RH Sensor Offset Zone 3
Equipment Minimum On Time
Heating Minimum Off Time
Compressor Minimum Off Time
Outdoor Temperature High Balance Point
Select Temperature
Outdoor Temperature Low Balance Point
Select Temperature
Stage Rate
Factor
First Stage Differential
Second Stage Differential
Third Stage Differential
Forth Stage Differential
Service HVAC Reminder
Recurrence
Description
Field adjustment of internal RH sensor.
Field adjustment of controlling temperature sensors.
Field adjustment of internal RH sensor.
Field adjustment of controlling temperature sensors.
Field adjustment of internal RH sensor.
Minimum on time for heating and cooling.
Minimum off time for heating.
Minimum off time for compressor protection.
Enable or disable high balance point. (Available if ODT is installed.)
If outside temperature is above the high balance point, the aux heat operation is
not allowed. (Available if high balance point is enabled.)
Enable or disable low balance point. (Available if ODT is installed.)
If outside temperature is below the low balance point, the compressor operation
is not allowed. (Available if low balance point is enabled.)
Accumulation of equipment run time in staging determination.
1 = more rapid staging of equipment (comfort).
5 = slower staging of equipment (economy).
First stage differential.
Second stage differential.
Third stage differential.
Fourth stage differential.
The period for displaying the HVAC Service reminder message.
Select number of months for displaying reminder.
Factory Default Settings (bold)
and Settings Range
0
-5 to 5
0°F (0°C)
-4 to 4°F (-2 to +2°C)
0
-5 to 5
0°F (0°C)
-4 to 4°F (-2 to +2°C)
0
-5 to 5
2 Minutes
1 to 5 Minutes
2 Minutes
1 to 5 Minutes
5 Minutes
1 to 5 Minutes
Enabled
Disabled
65°F (14.5°C)
0 to 80°F (-18 to 22°C)
Enabled
Disabled
20°F (-8°C)
0 to 60°F (-18 to 12°C)
Enabled
Disabled
2
1 to 5
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
Disabled
Enabled
12 Months
1 to 12 Months