6000 Series Sensor; Zone Number Selection; Installer Test; 6000 Series Control - Aprilaire 6000 Series Safety & Installation Instructions

Zone control system
Table of Contents

Advertisement

6000 SERIES SENSOR

ZONE NUMBER SELECTION

When the 6000 Series Sensor is connected and powered for the first
time it will display – and "select zone", the installer will be prompted
to select a zone number of 2 or 3. Pressing the up or down arrow will
display 2 or 3. The 6000 Series Sensor will revert to Room Temperature
Display 5 seconds after selecting a zone number.

INSTALLER TEST

There are two options for performing installer checkout test, from the 6000 Series Control or from the 6000 Series Hub.

6000 SERIES CONTROL

The Installer Test can be accessed from the Installer Menu. All
equipment outputs that are configured in the installer settings will be
turned on and off for testing equipment. Minimum on and off times are
not enforced while in this mode.

6000 SERIES HUB

The Installer Test can be accessed by pressing and holding the TEST
button located on the left side of the 6000 Series Hub for 7 seconds.
The installer test mode allows stepping through all outputs sequentially
via presses of the TEST button. The test will auto advance to next
step after 5 minutes. Minimum off times are not enforced in Installer
Test Mode. During Installer Test Mode the 6000 Series Hub will ignore
all commands from the 6000 Series Control. Certain steps will have
different outputs depending on the Equipment Type. When Installer Test
Mode is activated, the 6000 Series Hub will enter step 1 Stage 1 Heat.
Note: Installer Test Mode cannot be entered if the 6000 Series Hub has
not been previously connected to the 6000 Series Control.
FIGURE 23 – INSTALLER TEST BUTTON
INSTALLER
TEST BUTTON
90-2424
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

602060256010601560306040 ... Show all

Table of Contents