6000 SERIES CONTROL AND SENSORS INSTALLATION

LOCATION RECOMMENDATIONS

6000 Series Control and Sensors should be mounted:
• On an interior wall, in a frequently occupied space.
• Approximately 5 feet above floor.
• At least 18" from outside wall.
• Displays can be mounted to a vertical junction box.
Do not mount:
• Behind doors, in corners, or other dead air spaces.
• In direct sunlight, near lighting fixtures, or other appliances that give off heat.
• On an outside or unconditioned area wall.
• In the flow of a supply register, in stairwells, or near outside doors.
• On a wall with concealed pipes or ductwork.

MOUNTING

1. Remove the rear mounting plate.
2. Pull wires through the opening on the rear mounting plate.
3. Position and level the mounting plate of the display on the wall and mark the hole locations with a pencil.
4. Drill 1/4" holes and insert supplied anchors (drywall only).
5. Place mounting plate over anchors, insert and tighten screws.
6. Seal wire entry holes to prevent drafts affecting temperature readings.
FIGURE 19 – 6000 SERIES CONTROL MOUNTING PLATE
FIGURE 20 – 6000 SERIES SENSOR MOUNTING PLATE