TABLE 9: FRESH AIR SYSTEM SETTINGS

System Setting
Fresh Air Vent Installed?
Display Button?
Fresh Air Setup Type
Number of Bedrooms
Square Footage
Measured CFM
Calculated Minutes Per Hour
Override
Outdoor Temperature Sensor Installed?
High Vent RH Limit
RH
Low Vent RH Limit
RH
High Vent Temperature Limit
Temperature
Low Vent Temperature Limit
Temperature
HVAC Fan with Vent?
High Mixing Temperature
Temperature
Low Mixing Temperature
Temperature
Fresh Air Reminder
Recurrence
Description
Select whether ventilation is installed. (If set to No, no other ventilation settings
will be available.)
Note: only available if Fresh Air Installed is set to No.
ASHRAE: hourly ventilation time will be calculated using the ASHRAE
recommendations. Timed: hourly ventilation time will be determined based on
the Fresh Air Time value.
Selects the number of bedrooms to be used for the ASHRAE calculation.
Home size to be used for the ASHRAE calculation.
Selects the ventilation CFM to be used for the ASHRAE calculation.
Displays the Fresh Air Time calculated by the ASHRAE standard.
Manual adjustment of Calculated Minutes per Hour.
Select whether outdoor sensor is attached or not.
Selects whether ventilation is disabled if the indoor RH exceeds the indoor RH
limit. (Only available if Fresh Air Setup is set to Timed.)
Sets the high indoor RH limit for ventilation. (Only available if Fresh Air Setup is
set to Timed.)
Selects whether ventilation is disabled if the indoor RH exceeds the indoor RH
limit. (Only available if Fresh Air Setup is set to Timed.)
Sets the low indoor RH limit for ventilation. (Only available if Fresh Air Setup is
set to Timed.)
Selects whether ventilation is disabled if the outdoor temperature exceeds the
outdoor high limit. (Only available if an outdoor temperature sensor is installed.)
Sets the high temperature limit for ventilation. (Only available if an outdoor
temperature sensor is installed.)
Selects whether ventilation is disabled if the outdoor temperature exceeds the
outdoor low limit. (Only available if an outdoor temperature sensor is installed.)
Sets the low temperature limit for ventilation. (Only available if an outdoor
temperature sensor is installed.)
Selects whether ventilation forces the fan on. (Yes with high and low limits is
only available if Outdoor Sensor is set to Installed or Automation.)
Enables high mixing temperature. (Only available if HVAC Fan with Vent is set to
Yes with high and low limits.)
Sets the high mixing temperature. (Only available if Enable High Mixing
Temperature is set to Yes.)
Enables low mixing temperature. (Only available if HVAC Fan with Vent is set to
Yes with high and low limits.)
Sets the Low mixing temperature. (Only available if Enable Low Mixing
Temperature is set to Yes.)
The period for displaying the Fresh Air Service Reminder message.
Select the number of months for displaying reminder.
Factory Default Settings (bold)
and Settings Range
No
Yes
(6045M default is Yes)
Yes
No
Comfort
Code
3
1 to 10
2500 sq ft
500 to 7500 sq ft
110 CFM
30 to 250 CFM
6 to 60 Min/hr
(Calculated Minutes per Hour)
6 to 60 Minutes
Yes
No
Automation
Enabled
Disabled
55%
45 to 70%
Disabled
Enabled
20%
10 to 30%
Disabled
Enabled
100°F (38°C)
85 to 105°F (29 to 41°C)
Disabled
Enabled
10°F (-12°C)
-10 to 40°F (-24 to 6°C)
Yes
High & Low limits
No
Disabled
Enabled
80°F (26°C)
60 to 105°F (14 to 41°C)
Disabled
Enabled
40°F (6°C)
0 to 50°F (-18 to 12°C)
Disabled
Enabled
12 Months
1 to 12 Months
21