Low Voltage Wiring (Ac & Dc) Requirements; Condensate Drain Configuration - Trane Precedent WSC060ED Installation, Operation And Maintenance Manual

Packaged rooftop air conditioners - heat pump, 5-10 tons - 50 hz
Table of Contents

Advertisement

Figure 20. Duct cover
Insulation side up
Note: If unit is equipped with Return Air Smoke Detector,
refer to field conversion instructions for horizontal
discharge before installing return air duct.
Low Voltage Wiring (AC & DC)
Requirements
Install the zone thermostat, with or without switching
subbase.
Connect properly sized control wiring to the proper
termination points between the zone thermostat and
the unit control panel.

Condensate Drain Configuration

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
An evaporator condensate drain connection is provided
on each unit. Refer to
Figure 10, p. 16
the appropriate drain location.
The condensate drain pan is factory installed to drain
condensate to the back side of the unit. See
-
Figure 11, p.
17. It can be converted to drain condensate
out the front side of the unit or through the base.
To convert drain condensate out the front of unit:
1. Remove evaporator access panel and supply air access
panels.
2. Remove the support panel that the condensate drain
pan exits through.
3. Slide the condensate drain pan out of the unit and
rotate 180°.
4. Slide the condensate drain pan back into the unit, align
the drain with the grommeted opening in the rear
support panel and push until the coupling is seated in
the grommet.
RT-SVX39B-EN
Supply duct cover
Insulation side
down
Return duct
cover
-
Figure 11, p. 17
for
Figure 10, p. 16
5. Replace the front support panel by aligning the panel
with tabs in the raceway. Align the condensate drain
pan support in the grommeted hole as the panel is put
in place.
6. Replace evaporator access panel and supply air access
panels.
To convert drain condensate through the base
of unit:
1. Remove evaporator access panel and supply air access
panels.
2. Remove the support panel that the condensate drain
pan exits through.
3. Slide the condensate drain pan out of the unit.
4. Place on a level surface in the position it was removed
from the unit.
5. Remove the plug knockout in the bottom of the
drainpan to convert it to through the base drainage.
6. Plug the original condensate drain opening with a field
supplied 3/4" NPT plug.
7. Slide the condensate drain pan back into the unit, align
the drain support with the grommeted opening in the
rear support panel and push until the support is seated
in the grommet.
8. Replace the front support panel by aligning the panel
with tabs in the raceway. Align the plugged condensate
drain pan coupling in the grommeted hole as the panel
is put in place.
9. Replace evaporator access panel and supply air access
panels.
A condensate trap must be installed at the unit due to the
drain connection being on the "negative pressure" side of
the fan. Install the P-Trap using the guidelines in
A condensate drain line must be connected to the P-Trap.
Pitch the drain lines at least 1/2 inch for every 10 feet of
horizontal run to assure proper condensate flow. Do not
allow the horizontal run to sag causing a possible double-
trap condition which could result in condensate backup
due to "air lock" .
Figure 21. Condensate trap installation
Installation
Figure
21.
38.1
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Precedent wsc120ed

Table of Contents