Pre-Start

Space Temperature Averaging (ReliaTel™
only)
Space temperature averaging is accomplished by wiring a
number of remote sensors in a series/parallel circuit.
Using the BAYSENS016* or BAYSENS077*, at least four
sensors are required to accomplish space temperature
averaging. Example #1 illustrates two series circuits with
Figure 26. Examples
RT-SVX39B-EN
two sensors in each circuit wired in parallel. The square of
any number of remote sensors is required. Example #2
illustrates three sensors squared in a series/parallel circuit.
Using BAYSENS077*, two sensors are required to
accomplish space temperature averaging. Example #3
illustrates the circuit required for this sensor.
lists the temperature versus resistance coefficient for all
sensors.
Table 5, p. 27