BTL7-A/C/E/G_ _ _-M_ _ _ _-A/B/Y/Z(8)-S32/S115/S135/S140/KA_ _/FA_ _
Micropulse Transducer - Rod Style
10
Resetting all values (reset)
NOTICE!
Interference in function
Resetting the values while the system is running may
result in malfunctions.
► Stop the system before performing the reset.
The reset function can be used to restore all the settings
to the factory settings. For a reset the magnet may also
be located outside the measuring range.
1. Activate buttons
► Hold down any button for at least 3 s.
► Release button.
► Within 1 s, hold down
for at least 3 s.
⇒ Output indicates error value.
⇒ Buttons are activated.
If an error or an interruption occurs while
activating the buttons, allow a wait time of 12 s
before retrying.
2. Reset
Œ
► Hold down
and
⇒ Output indicates zero value.
⇒ All values are reset.
► Release buttons.
⇒ Current position value is displayed.
⇒ Buttons are locked.
22
english
Œ
and
simultaneously
for at least 6 s.
LED legend:
LED display
LED1 LED2 At 0 to 10 V
1
2
> 3 s
< 1 s
> 3 s
1
2
> 6 s
1
2
LED not on
LED green
LED flashing green
LED 1 and LED 2 flashing green-red simultane-
ously
Displayed values (example)
At 4 to 20 mA
5.39 V
10.80 mA
5.39 V
10.80 mA
10.50 V
3.60 mA
0.00 V
4.00 mA
8.43 V
15.67 mA