Siemens SIPART PS2 Compact Operating Instructions page 6

Non contacting sensor
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
WARNING
Unsuitable device for the hazardous area
Danger of explosion.
Only use equipment that is approved for use in the intended hazardous area and labelled accordingly.
WARNING
Loss of safety of device with type of protection "Intrinsic safety Ex i"
If the device has already been operated in non-intrinsically safe circuits or the electrical specifications have not been
observed, the safety of the device is no longer ensured for use in hazardous areas. There is a danger of explosion.
Connect the device with type of protection "Intrinsic safety" solely to an intrinsically safe circuit.
Observe the specifications for the electrical data on the certificate and/or in Chapter "Technical data (Page 15)".
3
Description
3.1
Function
The positioner facilitates the separate installation of the position detection system. The stroke or rotary angle is measured
directly at the actuator by means of a non contacting sensor. It is therefore possible to install the controller unit at some
distance away, e.g. on a mounting pipe or similar. The positioner is wired to the position detection system by means of an
electrical cable.
Such a separate installation is useful whenever the ambient conditions at the valve exceed the specified positioner values.
The NCS consists of a molded sensor for fixed installation and a magnet. The magnet is mounted to the spindle on linear
actuators, or to the stub shaft on part-turn actuators. The sensor housing is mounted onto the console on part-turn actuators
and to the bracket on linear actuators. The bracket can be a NAMUR type, or any other mounting bracket.
Auxiliary power is supplied to the NCS via the EMC filter module C73451-A430-D23 and EMC-compatibility is ensured at the
same time.
EMC filter module ordering options:
● Installed in the positioner; see Catalog FI 01
● For retrofitting in the positioner; Order No. C73451-A430-D23. For information on retrofitting the EMC filter module, refer
to the positioner operating instructions, chapter "Installation/Mounting".
Pneumatic line
Pneumatic line for double-action actuators
Position detection system (10 kΩ potentiometer, or NCS)
Electrical cable
Retrofittable EMC filter module (in the positioner)
Positioner
Figure 3-1
Separate installation of the NCS and positioner
6
SIPART PS2 Non Contacting Sensor (NCS)
A5E00097485-09, 09/2014