Connecting
NOTICE
Incorrect mounting
The device can be damaged, destroyed, or its functionality impaired through improper mounting.
Before installing ensure there is no visible damage to the device.
Make sure that process connectors are clean, and suitable gaskets and glands are used.
Mount the device using suitable tools. Refer to the information in Technical specifications (Page 15) for installation
torque requirements.
Requirements
You need the EMC filter module with article number C73451-A430-D23 to connect the NCS to the positioner. The positioner
supplies auxiliary power to the NCS via the EMC filter module.
Wiring diagram
Positioner (open state)
Vcc: Yellow
Vref: Green
Vpos: Black
Ground: Brown
EMC filter module C73451-A430-D23
Figure 5-1
Example of connecting the NCS to the EMC filter module
Procedure
The NCS is equipped with a shielded four-pole cable. Wire this cable to the positioner as follows:
1. Feed the four-pole NCS cable
the positioner version.
SIPART PS2 Non Contacting Sensor (NCS)
A5E00097485-09, 09/2014
through the union nut and the cable gland. Note: The type of cable gland depends on
Cable clamp
Screw F3x8
Cable gland
Four-pole NCS cable
Non Contacting Sensor (NCS)
Cable shielding lug
13