Advertisement

3.3

Rack Mounting Series 505 Base

PPX:505–6516,
16-Slot Base
Installing Series 505 System Hardware
3-4
Use the following steps, and Figure 3-1, for mounting the base in a standard
19-inch rack.
1.
Align two bracket holes with two screw holes located on the sides of
base.
2.
Secure each bracket to base with two screws installed through the
bracket holes.
3.
Position the base in the 19-inch rack. Depth of base is 7.99 inches
(20.3 cm).
NOTE: There should be at least 6 inches (15.24 cm.) of clearance at the top
and bottom of base for adequate airflow.
4.
Align two bracket slots with two screw holes located on each side of the
19-inch rack. See Figure 3-1.
5.
Secure each bracket to the 19-inch rack with two screws installed
through the the bracket slots. See Figure 3-1.

Figure 3-1 Mounting Base to Standard 19-inch Rack

TI545/TI555 System Manual