INSTALLATIONS
AERAULIC CONNECTIONS
Connect the channels using the appropriate outlet flange. It is advisable to interpose a flexible connection
between the car and channels to not transmit the vibrations. Channels must be appropriately sized
(according to the prevalence of the machine) and insulated to prevent condensation and deaden the noise
propagation.
To connect the suction channels, you need a special accessory, the flange shooting (FRA). If you connect
the channels in another way, it is likely to compromise the accessibility of the filter or damage the machine.
OUTLET FLANGE
Outlet Flange
IDRAULIC CONNECTIONS
The unit is equipped with coil suitable to work with water, water mixed with glycol. In wither season there is
the possibility to empty the water circuit if there is a risk of icing inside the battery.
To avoid the formation of condensation on the surfaces of the machine during the summer period, when the
fan is not on, it is recommended to stop the flow of chilled water in the coil through a motorized valve.
All the pipes, in particular those of the chilled water, must be insulated to prevent dripping of condensation.
For ease of maintenance, it is advisable to provide manual ball valves, in order to exclude the unit from the
plant .
While connecting pipe, don't twist coils and valves, it is recommended to use two wrench.
Valves can be supplied in the kit (to be assembled by the installer) or by delivered by the installer.
When the installation is completed and the hydraulic system has been loaded, it is necessary to remove the
air inside the coil using the appropriate valve. Repeat the purging procedure after the activation of the
circulation pump, as long for to be sure all air bubbles will be completely eliminated.
16