Automatic Transfer Switches - IBM XIV Gen3 Series Planning Manual

Table of Contents

Advertisement

Feature codes
The following table provides feature codes and descriptions for each available ATS.
It also lists the feature codes for each of the main-power cables that are associated
with that specific ATS.
Table 23. Automatic transfer switches
Automatic
transfer
switch feature
code
9890
9891
9892
9894
The following table provides the feature codes and description details for each
main-power cable.
Note: The main-power cables are provided with the connector part numbers listed
in the following table. Receptacle part numbers in the following table are
recommended. Although equivalent receptacles can be used, it is the responsibility
of the customer to verify compatibility.
Table 24. Main-power cables
Main-
power
cable
ATS
feature
feature
code
code
Description
9811
9890
Main-power cable for United States, Canada,
Latin America, and Japan; single-phase, 60 A,
two wires + ground with plug
9813
9890
Main-power cable for Europe, Middle East,
and Asia/Pacific (except Japan); single-phase,
60 A, two wires + ground, hard wired
Description
ATS for worldwide use;
single-phase, 60 A
ATS for United States, Canada, Latin
America, and Japan; three-phase
delta, 60 A
ATS for Europe, Middle
East,Asia/Pacific (except Japan),
Australia, and New Zealand;
three-phase wye, 30 A
ATS for United States, Canada, Latin
America, and Japan; three-phase
delta, 30 A
Ground
Feature codes for associated
main-power cables
9811
9813
9820
9822
9824
Connector
Wall receptacle
Hubbell
Hubbell
HBL360P6V04
HBL360R6W
Hard wired or
Not applicable
uses
client-provided
connector
Chapter 6. Installation site requirements
Inline
receptacle
Hubbell
HBL360C6W
Not applicable