Installation - Toshiba Carrier MMD-AP0074BH2UL-1 Installation Manual

Multi type air conditioner
Hide thumbs Also See for Carrier MMD-AP0074BH2UL-1:
Table of Contents

Advertisement

Available languages

Available languages

4

Installation

WARNING
• Install the air conditioner certainly at a place to sufficiently withstand the weight.
• If the strength is insufficient, the unit may fall down resulting in human injury.
• Perform a specified installation work to guard against an earthquake.
• An incomplete installation can cause accidents by the units falling and dropping.
• Do not install the indoor unit in the way that it takes in the air in the ceiling and provides it into the room. The indoor
unit must be installed in the way that it takes in the air from the room and returns it back to the room.
CORRECT
1 room
• This unit and it's ducting (supply and return air) are intended for use in one room only.
CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering
cloth or other material to not damage the unit.
• To move the indoor unit, hold the hooking brackets (4 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, resin parts or other parts).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
• To install vibration isolation material to hanging bolts, confirm that it does not increase the unit vibration.
 External dimensions
Air filter slot
9-EN
INCORRECT
INCORRECT
Unit: in (mm)
Hanging bolt pitch B
Unit external dimension A
5.5" (140)
Air discharge flange outside C
Hanging bolt 4-M0.4"(10)
(locally procured)
– 5 –
<Back air intake>
Drain pipe connecting port
VP25(Polyvinyl chloride tube:
External Dia,1-1/4" Internal Dia,1"
Air discharge
side
Refrigerant pipe connecting
port ØF
(Gas side)
Refrigerant pipe connecting
port ØG
(Liquid side)
<Under air intake>
Air discharge side
1.7" (44)
1.9" (49)
Model MMD-
AP007, AP009, AP012
AP015, AP018
AP021, AP024, AP030,
AP036, AP042, AP048
1" (25)
Unit external dimension 31.5" (800)
1.6" (41)
Hanging bolt pitch 27.6" (700)
2" (50)
25.1" (638)
19.6" (498)
15.1" (384)
Ø1" (26) Hole for control wire
and remote control wiring
Ø7/8" (22.2) Hole for power supply cable
Air intake flange outside D
Z view
6.3"
(159)
9.6" (243.2)
12.6" (320)
Air intake side
A
B
C
27.6" (700)
30.2" (766)
19.7" (501.6)
24.5" (621.6)
39.4" (1000)
42" (1066)
31.6" (801.6)
36.3" (921.6)
53.2" (1350)
55.7" (1416)
45.4" (1151.6)
50.1" (1271.6)
2.2" (57)
2.4" (59)
Air filter slot
1.2" (30)
Z
Air intake
side
Air intake flange
Air filter slot
Air intake flange
3.6" (91)
D
F
G
3/8" (9.5)
1/4" (6.4)
1/2" (12.7)
1/4" (6.4)
5/8" (15.9)
3/8" (9.5)
10-EN