Parameter assignment/addressing

4.1

Parameters

GSDML file parameters
Table 4- 1
Parameters for the digital input module (GSDML file)
Parameters
Diagnostics
missing supply voltage L+
Diagnostics
short-circuit to ground
Diagnostics
wire break
1
Operating mode
Input delay
BaseUnit with incoming supply
voltage
If you use a simple switch, you need to connect a resistor in parallel so that the wire break diagnostics applies in the
1
open state (sensor resistance for the wire break diagnostics: 25 kΩ to 45 kΩ).
DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0)
Manual, 03/2012, A5E03574157-01
Value range
disable
enable
disable
enable
disable
enable
Channel
deactivated
Channel activated
none
0.05 ms
0.1 ms
0.4 ms
0.8 ms
1.6 ms
3.2 ms
12.8 ms
20 ms
No
Yes
Default
Configuration in
disable
Yes
disable
Yes
disable
Yes
Channel activated
Yes
3.2 ms
Yes
No
No
Efficiency range
RUN
Module
Module
Module
Channel
Channel
Module
4
13