EN – Main switch and EMC C1 filter options installation supplement 21
R3...R4
Option layout
Options are shown with the covers removed in the following figures.
R3...R4, +B056+F278
A2b
A1
A2
O
OFF
2T1
2T1
4T2
4T2
6T3
A2a
C
A1
Main switch
A2
Main switch auxiliary contact. Connector 13 at the bottom (A2a) and connector 14 on
the top (A2b).
B1
EMC C1 filter
B2
EMC C1 filter terminal block
B3
EMC C1 filter toroidal core
C
Grounding terminal for the input cable
Connect the power cables
See the figures in section
the step numbers.
1. Remove the rubber grommets from the cable entry.
2. Motor cable: Prepare the motor cable according to the R1...R5 quick installation
and start-up guide of the drive, except the text below in this step. See figure 2 in
section
R3...R4 Figures
+B056+F316, +B056+E223: Lead the cable through the toroidal core.
Note: Do not strip the cable under the clamp (2a), otherwise the toroidal core
does not remove interference from the motor cable.