iii. General
System Settings: General
Service Password:
1000
Range Unlock Password:
1000
Side Bar Light:
On
Fire Contact:
Fire Sys Discharge Only
Software
Version:
v1.00 04/02/2019
Service Password: Password for entering into service
settings screens. (Default 1000).
Range Unlock Password: Password for unlocking range,
if PW/Auto Range Deactivate is enabled.
(Default 1000).
Side Bar Light: Blue side bar light can be turned on or
off. This helps indicate (when screen backlight turns off)
that the hood is still operational to the user. (Default On).
Fire Contact: The dry fire contacts (terminal blocks C6,
NO6, and NC6) typically used for building fire alarm
panel integration can switch state in the event of either
a fire system discharge only, or can be configured to
switch state for both fire system trouble faults and fire
system discharges. (Default is Fire System Discharge
Only).
Software Version: This indicates the software version
running on the system controller.
iv. Time and Date
System Settings: Time and Date
Update Time:
5
:
30 AM
Update Date:
4
/
2
/
2019
Update Time: Adjust time (hours, minutes, AM/PM) for
system controller.
Update Date: Adjust date (months, days, year) for
system controller.
C. Fault Log
Fault Log
From : 03/24/19 - 15:43:32
Duration :
1 Min
To :
03/24/19 - 15:43:33
Backward
Alarm Reset
The fault log records and stores previous faults on the
system. Press the blue arrow to navigate back to the
Service Settings menu.
Balance Exhaust Fan
(within Systems Settings: Setpoints)
Balance Exhaust Fan
Max Speed %:
70
%
Design Plenum Pressure:
0.21
in. wc.
Designed Exhaust Airflow:
250
CFM
Connect one end of manometer to plenum
pressure port behind filter and take reading.
Adjust max speed as necessary to match the
design plenum pressure reading above.
Upon entering this menu, the exhaust fan will turn on
and ramp to the max speed percentage shown. Connect
manometer to plenum pressure port, then adjust max
speed value to match the manometer reading with the
"Designed Plenum Pressure" reading on the screen
in order to obtain "Designed Exhaust Airflow". When
finished, press blue arrow button to navigate back to
System Settings: Setpoints screen.

Fire Prevention Tips

If you must leave the kitchen when frying food, turn the
burner off or remove the pan from the burner until you
return.
In case of a grease fire:
NEVER attempt to move a pan of cooking grease that is
already on fire from the kitchen range.
NEVER attempt to extinguish a grease fire with water.
Instead, alert the other occupants and evacuate. Let the
fire suppression system installed in the hood extinguish
the range top fire. Wait at least 30 minutes after a
cooking fire has been extinguished before approaching
your range.