Accurex XRRS Series Installation, Operation And Maintenance Manual page 22

Fire ready hood
Table of Contents

Advertisement

B. System Settings
i. Configuration
System Settings: Configuration
Size:
30"
Disconnect Type:
Electric
NFPA 101 Compliant:
No
Ventilation Type:
Internal Fan - Front Recirc
PW/Auto Range Deactivate:
Disabled
Size: Hood length, selectable between 30 or 36 inches.
(Default based on configuration).
Disconnect Type: Range utility disconnect type,
selectable between electric or gas. (Default based on
configuration).
NFPA 101 Compliant: Selectable between no or yes for
NFPA 101 compliance. (Default based on configuration).
Ventilation Type: Selectable between Internal Fan –
Front Recirculation, Internal Fan – Rear Discharge,
or External Fan – Inline/By Others. (Default based on
configuration).
PW/Auto Range Deactivate: Selectable between
enabled or disabled, this provides password protection
for unlocking the range, and automatically will shut it
off after a countdown timer expires. (Default based on
configuration).
22
Fire Ready Hood
ii. Setpoints
System Settings: Setpoints
Min Fan Speed (% of Max):
60
%
Max Fan Speed:
70
%
Auto On Temp Setpoint:
115.0
F
Auto Fan Off:
Enabled
High Temp Alarm Setpoint:
180.0
F
Current Hood Temperature:
75.0 F
Min Fan Speed (% of Max): Percentage of maximum
speed when fan is running at low speed. (Default 60%).
For example if this is set to 60%, and max speed is set
to 70%, the actual minimum speed setting will be 60%
of 70%, or 42% (4.2VDC output control signal to ECM
fan).
Max Speed %: Speed percentage when fan is running
at max speed. (Default based on configuration)
This value can only be adjusted in the Balance Exhaust
Fan screen. Press the "Balance Exhaust Fan" button to
enter into this screen. See page 23 for details.
Auto On Temp Setpoint: When hood temperature
reaches this setpoint, the fan (if not already on) will turn
on, and force the fan to high speed. (Default 115°F).
Auto Fan Off: When enabled, this will allow the fan to
shut off automatically if the fans are turned off manually
when temperatures are above the Auto On Temp
Setpoint, once the temperature decreases below the
setpoint and stays below it for the Fan Auto Off Delay
time. (Default Enabled).
High Temp Alarm Setpoint: Upon hood temperatures
reaching this setpoint, the range will automatically be
locked. (Default 180°F).
Current Hood Temperature: Displays current
temperature of hood.
Balance
Exhaust
Fan