Arming The System - Accurex XRRS Series Installation, Operation And Maintenance Manual

Fire ready hood
Table of Contents

Advertisement

Arming the System

NOTE
System arming is typically performed by factory
authorized fire equipment distributor during startup.
Do not tamper with the fire suppression system after
the initial startup unless authorized to do so.
To arm the range, do the following:
1. Once hood and hood components are installed,
wired, and fan is balanced (if necessary), drop the
hood into the service position, (instructions on page
22) and turn on all breakers feeding the hood and
hood components.
2. Remove the black cover from the fire suppression
control board enclosure inside the hood (on left side
of hood if looking at the hood front face).
FIRE SUPPRESSION
CONTROL BOARD
ENCLOSURE
LOOSEN SPRING
LOADED THUMB
SCREW TO
ACCESS FIRE
SUPPRESSION
CONTROL BOARD
TOP VIEW
3. With the cylinder pull-pin still installed in the agent
tank (mounted beneath the fire suppression board),
and 9V battery installed on the fire suppression
control board, initiate a diagnostic test by press
and release of the "TEST" button (also on the fire
suppression board).
FIRE SUPPRESSION
CONTROL BOARD
ENCLOSURE
(INSIDE HOOD)
PULL PIN CURRENTLY
INSTALLED IN
AGENT TANK
FIRE SUPPRESSION
CONTROL BOARD
"TEST" BUTTON
18
Fire Ready Hood
BACK WALL
PULL
PIN
RESET
BUZZER
GREEN
LED
RED
LED
BATTERY
TEST
4. The test should fail and issue six chirps, indicating
that the pull pin has not been removed from the tank.
If the result is a lesser number of chirps followed by
the series of six chirps, then some item other than
the pull pin has failed and the system should be
troubleshot before proceeding further (see Diagnostic
Failure Codes, page 25).
5. After troubleshooting, re-test until only the 6 chirp
diagnostic failure code occurs.
6. Verify that the fuel shut-off is powered (breaker is on)
and all burners on the range are off.
7. Remove wing screws that hold
the fire suppression control
board enclosure in place above
the wet chemical tank. Without
disconnecting any cables, slide
the control board assembly
towards the middle of the hood
and down so it's next to the tank,
revealing the tank assembly.
8. Check and make sure the solenoid release latch
is engaged and holding the release latch up, then
remove the pull pin from the agent cylinder and insert
the pull pin in its socket on the PCU board.
PULL PIN
CAREFULLY
FROM TANK
ASSEMBLY
9. If the push and release of the "RESET" button yielded
a green light, leave the pull pin in the CPU. Unlock the
range via the user interface.
FIRE SUPPRESSION
CONTROL BOARD
ENCLOSURE
(INSIDE HOOD)
"RESET"
BUTTON
PULL
PIN
FIRE
SUPPRESSION
RESET
BUZZER
CONTROL
GREEN
LED
BOARD
RED
LED
BATTERY
TEST
WHILE REMOVING
PIN, HOLD SOLENOID
RELEASE LATCH
UNDER RELEASE
LEVER. MAKE
CERTAIN IT'S
SUPPORTING
THE LEVER.
TANK
PULL PIN FROM TANK
(MOUNTED BELOW
FIRE SUPPRESSION
CONTROL BOARD)
LOCATION
OF WING
SCREWS

Advertisement

Table of Contents
loading

Table of Contents