Accessories

Remote Mounted User Interface (if applicable)
There will be one 8½ ft. plug and play cable with an
light blue label attached to the hood. Run the cable
through a one inch knockout in the controls j-box,
run behind the wall and connect to the back of the
user interface. Mounting instructions can be found on
page 11.
FIRE READY
HOOD
BACK OF USER
INTERFACE
R12
TELEPHONE
CONNECTOR
USER
INTERFACE
Manual Pull Station (if applicable)
Manual pull station will be provided with a 30 ft. plug
and play cable. Run this behind the wall through a
one inch knockout in the controls j-box, then into the
hood and connect to "REMOTE PULL" port on fire
suppression control board.
FIRE READY
HOOD
INSIDE MANUAL
PULL STATION
J-BOX
FIRE
FIRE
PULL
MANUAL PULL
STATION
Horn Strobe (if applicable)
There will be one 8 ft. plug and play cable attached
to the horn strobe itself. Run the cable to the gas or
electric shut off assembly box and connect to the
receptacle labeled "ALARM / STROBE".
ALARM / STROBE
115 VOLT - 5 AMP
OR
RANGE
115 VOLT - 15 AMP
LEFT SIDE VIEW -
GAS SHUT OFF
ASSEMBLY BOX
(MOUNTED BEHIND RANGE)
8.5 FT. CABLE
ATTACHED TO
HOOD
VALVE
(TANK SOLENOID)
30 FT. CABLE
BLDG
REMOTE
SHUT-OFF
ALARM
RF
PULL
PLUGS INTO
"REMOTE PULL" ON
FIRE SUPPRESSION
CONTROL BOARD
INSIDE
HOOD
F
I
R

HORN STROBE

E
8 FT. CABLE
LEFT SIDE VIEW -
ELECTRIC SHUT OFF
ASSEMBLY BOX
(MOUNTED BEHIND RANGE)
Other External Devices
Supply Fan Interlock Contacts
1. R and G terminal
2. Dry, normally open contact closes when supply
fan should run – can be used to drive a device that
controls a supply fan if MUA is necessary
3. Contacts rated to 5A and 250VAC
11
R
R4
G
14

Fire/Fault Contacts

1. C6 and NO6 terminal blocks - Dry, normally open
(N.O.) contact closes on fire/fault
2. C6 and NC6 - Dry, normally closed (N.C.) contact that
opens on fire/fault
3. Contacts rated to 5A and 250VAC
U1 PLC
CONTACT
See page 18 for additional details.
C6
NO6
NC6