CAUTION
Carefully remove the pull pin from the tank, holding
the release latch in place, as to not accidentally cause
a fire system discharge.
ATTENTION
Retirer soigneusement la goupille du réservoir tout
en maintenant le verrou de déblocage en place pour
ne pas provoquer accidentellement une décharge du
système d'extinction d'incendie.
10. The final step for verification is to turn on a range
burner, then momentarily push and release the
"TEST" button. If there are no failures detected, the
fire suppression board will run a shutoff sequence
(the alarm will sound for 10 seconds and shut off
fuel to the stove followed by a chirp every minute).
This allows complete verification of the system
function all the way to the fuel shut-off but without
the chemical agent dump. If the stove does not
shut-off (burner shuts off and begins to cool down),
additional troubleshooting is required.
11. Reset the CPU board by pressing the "RESET"
button and confirm the green indicator momentarily
lights up.