Electrical Connections

CAUTION
Electrical installation should be performed by a
licensed electrician. Shut off power at the main
breaker to prevent electrical shock when accessing
electrical connections. All field installation and wiring
of electrical equipment must be done to meet NEC
and local codes.
ATTENTION
Confier les travaux d'installation électrique à un
électricien qualifié. Couper l'alimentation électrique
au disjoncteur principal pour éviter des chocs lorsqu'il
faut avoir accès aux connexions électriques. Toute
l'installation en chantier et câblage de l'équipement
électrique doivent être effectués conformément au
code national de l'électricité et aux codes locaux.

Hood Power

1. Run 115VAC from 15A breaker through a one inch
knockout in the control j-box behind the hood
mounting bracket, then into the hood.
2. Land the hot on terminal H1, neutral on terminal N1,
and ground on green GND terminal. Make sure there
is enough slack in the wire to prevent tension on it
when the hood is dropped in the service position; the
hood should be supported by the safety cable and
link and not by electrical wiring.
H1
L1
N1
N
GND
GND
Fan Power
Integral Fan – Front Recirculation or Rear
Discharge
If provided with an internal fan, the fan will be wired
from the factory.
External Fan – Inline
If provided with an external inline fan, the hood will be
provided with a 50 ft. 4-wire plug and play cable with
an orange label. Connect this cable to the orange plug
and play harness at the fan, run it down to the hood and
through the a two inch knockout in the controls j-box.
Connect to the orange plug and play harness in the
hood.
DUCTWORK
(BY OTHERS)
EXTERNAL INLINE
FAN
DUCTWORK
(BY OTHERS)
50 FT. CABLE
FROM HOOD
LABELED "FAN"
CONTROL INPUT:
115 VAC, 15AMPS
FROM BREAKER
RED (+10VDC)
YELLOW (0-10VDC +)
BLUE (0-10VDC -)
WHITE (TACH OUT)
GREEN (GND)
BLACK/BROWN (115VAC )
BLUE (115VAC)
FAN
1 2 3 4
QUICK
CONNECTOR
CONNECTOR
CONNECTOR
1 2 3 4
1 1 1
2 2 2
3 3 3
4 4 4
External Fan – Fan by Others
If configured for an external fan by others, there will be
a 50 ft. 4-wire plug and play cable with an orange label.
Connect this to the orange harness in the hood, run it
through a two inch knockout out of the controls j-box
and out to the fan. Signals for each wire are shown:
U1 PLC
INSIDE
HOOD
1 FT. FAN
HARNESS 1
QC1
1
U10
1
1
FAN CABLE
2
NO2
2
2
ORANGE
3
N1
3
3
(50 FT.)
4
GND
4
4
NOTE
115VAC on wires 2 and 3 in a 'fan by others' harness
can drive a motor with a max FLA of 5 amps. If driving
ALARM / STROBE
115 VOLT - 5 AMP
a motor that draws more than 5 amps at full load,
RANGE
utilize this signal to drive a motor starter with contacts
LEFT SIDE
POWER
VIEW
CORD
that can handle larger amperages (motor starter to be
provided by others).
RANGE
115 VOLT - 15 AMP

Range Disconnect

Gas (if applicable)
1. If gas range has a 115VAC cord, plug this cord into
the gas shut off assembly box 115VAC receptacle
labeled "RANGE".
ALARM / STROBE
115 VOLT - 5 AMP
RANGE
LEFT SIDE
POWER
VIEW
CORD
RANGE
115 VOLT - 15 AMP
2. If not already done, plug gas valve 1.5 ft. whip into
5 ft. gas valve cord coming off of bottom of the gas
shut off assembly box.
GAS SHUT OFF
ASSEMBLY BOX
(FRONT VIEW)
60" (5 FT)
GAS
VALVE
CORD
3/4" NPT
GAS VALVE
GAS PIPING TO RANGE
3/4"
1 FT. FAN
HARNESS 2
QC2
1
1
1
1
0-10VDC + SIGNAL
2
2
115VAC L (5A RES. MAX)
2
2
3
3
115VAC N (5A RES. MAX)
3
3
4
4
0-10VDC - SIGNAL (GND)
4
4
RANGE (BY OTHERS)
RANGE 115VAC
POWER CORD
(IF PROVIDED
WITH RANGE)
GAS SHUT OFF
ASSEMBLY BOX
RANGE (BY OTHERS)
RANGE 115VAC
POWER CORD
(IF PROVIDED
WITH RANGE)
GAS SHUT OFF
ASSEMBLY BOX
MOUNTED
BEHIND RANGE
18" (1.5 FT)
WHIP TO
GAS VALVE
GAS PIPING TO VALVE
Fire Ready Hood
13

Advertisement

Table of Contents
loading

Table of Contents