Arming the System

NOTE
System arming is typically performed by factory
authorized fire equipment distributer during startup.
Do not tamper with the fire suppression system after
the initial startup unless authorized to do so.
To arm the range, do the following:
1. Once hood and hood components are installed,
wired, and fan is balanced (if necessary), drop the
hood into the service position, (instructions on page
20) and turn on all breakers feeding the hood and
hood components.
2. Remove the black cover from the fire suppression
control board enclosure inside the hood (on left side
of hood if looking at the hood front face).
FIRE SUPPRESSION
CONTROL BOARD
ENCLOSURE
LOOSEN SPRING
LOADED THUMB
SCREW TO
ACCESS FIRE
SUPPRESSION
CONTROL BOARD
TOP VIEW
3. With the cylinder pull-pin still installed in the agent
tank (mounted beneath the fire suppression board),
and 9V battery installed on the fire suppression
control board, initiate a diagnostic test by press
and release of the "TEST" button (also on the fire
suppression board).
FIRE SUPPRESSION
CONTROL BOARD
ENCLOSURE
(INSIDE HOOD)
PULL PIN CURRENTLY
INSTALLED IN
AGENT TANK
FIRE SUPPRESSION
CONTROL BOARD
"TEST" BUTTON
4. The test should fail and issue six chirps, indicating
that the pull pin has not been removed from the tank.
If the result is a lesser number of chirps followed by
the series of six chirps, then some item other than
the pull pin has failed and the system should be
troubleshot before proceeding further (see Diagnostic
Failure Codes, page 21).
5. After troubleshooting, re-test until only the 6 chirp
diagnostic failure code occurs.
6. Verify that the fuel shut-off is powered (breaker is on)
and all burners on the range are off.
16
Fire Ready Hood
BACK WALL
PULL
PIN
RESET
BUZZER
GREEN
LED
RED
LED
BATTERY
TEST
7. Remove wing screws that hold
the fire suppression control
board enclosure in place above
the wet chemical tank. Without
disconnecting any cables, slide
the control board assembly
towards the middle of the hood
and down so it's next to the tank,
revealing the tank assembly.
8. Check and
make sure
PULL PIN
CAREFULLY
FROM TANK
the solenoid
ASSEMBLY
release latch
is engaged
and holding
the release
latch up, then
remove the
pull pin from the agent cylinder and insert the pull pin
in its socket on the PCU board.
FIRE SUPPRESSION
CONTROL BOARD
ENCLOSURE
(INSIDE HOOD)
"RESET"
BUTTON
PULL
PIN
FIRE
RESET
SUPPRESSION
BUZZER
CONTROL
GREEN
LED
BOARD
RED
LED
BATTERY
TEST
9. If the push and release of the
"RESET" button yielded a green
light, leave the pull pin in the CPU. Unlock the range
via the user interface.
CAUTION
Carefully remove the pull pin from the tank, holding
the release latch in place, as to not accidentally cause
a fire system discharge.
ATTENTION
Retirer soigneusement la goupille du réservoir tout
en maintenant le verrou de déblocage en place pour
ne pas provoquer accidentellement une décharge du
système d'extinction d'incendie.
10. The final step for verification is to turn on a range
burner, then momentarily push and release the
"TEST" button. If there are no failures detected, the
fire suppression board will run a shutoff sequence
(the alarm will sound for 10 seconds and shut off
fuel to the stove followed by a chirp every minute).
This allows complete verification of the system
function all the way to the fuel shut-off but without
the chemical agent dump. If the stove does not
shut-off (burner shuts off and begins to cool down),
additional troubleshooting is required.
11. Reset the CPU board by pressing the "RESET"
button and confirm the green indicator momentarily
lights up.
12. Make sure all burners are off, then unlock the range
via the user interface.
WHILE REMOVING
PIN, HOLD SOLENOID
RELEASE LATCH
UNDER RELEASE
LEVER. MAKE
CERTAIN IT'S
SUPPORTING
THE LEVER.
TANK
PULL PIN FROM TANK
(MOUNTED BELOW
FIRE SUPPRESSION
CONTROL BOARD)
LOCATION
OF WING
SCREWS