Internal Relay Fault - ABB Arc Guard System TVOC-2 Installation And Maintenance Manual

Hide thumbs Also See for Arc Guard System TVOC-2:
Table of Contents

Advertisement

ABB
ARC GUARD SYSTEM™ – T VOC-2 INSTALL ATION AND MAINTENANCE GUIDE
Connecting electrical connections
WARNING
Make sure that supply voltage is switched off!
This section describes how to connect the electrical
connections to the Arc Monitor and to the Arc Guard
System.
Connecting HMI;
See: "Mounting the HMI" on page 20.
Connecting optical detector
See: "Connecting optical detectors" on page 23.
Connecting extension module (option)
See: "Connecting extension module (option)" on
page 24.
Connecting Current Sensing Unit (option)
See: "Connecting CSU cable" on page 24.
Electrical connections are:
1.
Internal Relay Fault, ( IRF, K1)
2.
Trip Signal relays, ( K2, K3)
3.
Trip contact, (K4, K5, K6)
4.
Power supply
They are situated on top of the Arc Monitor.
Connecting the Arc Monitor
WARNING
Make sure that supply voltage is switched off!
First connect the trip signal relays and trip contacts.
Follow the steps below:
1.
Connect wires for Internal Relay Fault, IRF, trip
signal relays (K2, K3) and trip contacts (K4, K5, K6).
2.
Use a torque of 0.5 NM
3.
Use a screwdriver 2.5 x 0.6 mm (0.98 x 0.23 inches)
4.
Cable area 0.2 - 2.5 mm² (0.078 x 0.98 inches²).
5.
Connect cable for IRF, K1 to terminal number,
14,12,11.
6.
Connect cable for K2 to terminal number 24, 22, 21.
7.
Connect cable for K3 to terminal number 34, 32, 31.
8.
Connect cable for K4 to terminal number 43, 44.
9.
Connect cable for K5 to terminal number 53, 54.
10.
Connect cable for K6 to terminal number 63, 64.
1
2
3
Figure 15
Electrical connections
2,5x0,6
7
0,2 ... 2,5 mm
0,2 ... 2,5 mm
0,5 Nm
Figure 16
Connecting the trip signal relays and trip contacts
14 12 11
24 22 21
34 32 31
Figure 17
Connecting the trip signal relays and trip contacts
25
4
1SFC170011M0201
2
14 12 11
24 22 21
34 32 31
43 44
53 54
63 64
2
1SFC170011M0201
43 44
53 54
63 64
1SFC170011M0201

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents