Mounting TVOC-2
This section describes the procedure to mount and
connect the Arc Monitor.
The procedure is divided into following components:
•
Arc Monitor
•
Human Machine Interface, HMI
•
Detectors
•
Extension
•
Current Sensing Unit, CSU
Placing Arc Monitor
The Arc Monitor can be mounted anywhere in the
switchgear, for example in the breaker cubicle or in a
separate control cabinet.
Mounting Arc Monitor
This section describes how to mount the Arc Monitor at
its location.
The Arc Monitor can be mounted on:
•
A wall
•
DIN Rail
Mounting on wall
Follow the steps below to mount the Arc Monitor on the
wall:
1.
Predrill holes in wall to fit screws 5M.
See figure 1 for dimensions.
2.
Place the Arc Monitor on the wall.
3.
Screw in each corner of the monitor.
4.
Use a torque wrench and torque the screws to
2,4Nm.
Mounting on a DIN rail
Follow this procedure to mount the Arc Monitor on a DIN
rail:
1.
1
Hook the Arc Monitor to the DIN rail.
2.
Pull the barrier down, between detector 5 and 6.
2
3.
3
Snap the Arc Monitor on to the rail then release
the barrier.
2,4 Nm
Figure 1
Mounting on wall
2
Figure 2
Mounting on DIN rail
19