Attaching The Mounting Plates To The Redundant Ac-Power Switch; Labeling The Cables; Attaching The Mounting Plates - IBM 2145-8F2 Hardware Installation Manual

System storage san volume controller
Hide thumbs Also See for 2145-8F2:
Table of Contents

Advertisement

The following topics describe the redundant ac-power switch installation tasks in
the order that they must be performed:
1. Attach the mounting plates to the redundant ac-power switch.
2. Label the cables.
3. Connect the power input cables to the redundant ac-power switch.
4. Install the redundant ac-power switch in the rack.
5. Connect the redundant ac-power switch to the site power.
6. Test the redundant ac-power switch to ensure that it automatically switches
Attaching the mounting plates to the redundant ac-power
switch
Attach the mounting plates to the redundant ac-power switch before you label the
cables.
Perform the following steps to attach the mounting plates to the redundant
ac-power switch:
Attach each of the two mounting plates to the redundant ac-power switch using
three M3 Torx T8 head screws. Position the mounting face on the side of the
redundant ac-power switch containing the output power sockets. See Figure 23.
Figure 23. Attaching the mounting plates

Labeling the cables

You must label each end of the two redundant ac-power switch input-power cables
before you connect the input-power cables to the redundant ac-power switch.
32
IBM System Storage SAN Volume Controller: Models 2145-8F2 and 2145-8F4 Hardware Installation Guide
1
2
power supplies when the main power source fails or is restored.