Air Conditioning Control System (Touch Screen Controller)
 Before Installation
Confirm that all the parts listed below are included in the package.
Included Items
No.
Component name
1
Main unit
2
Power adapter
3
Owner's Manual
4
Installation Manual
5
DVD-R
6
Fixing screw
7
Fixing screw
8
Closed end connector
9
Binding band
10
Double-sided tape
Wiring specifications
Use the following wiring material to connect signal wires and power supply wires. (Locally procured)
No.
Wiring
1
For TCC-LINK
2
For RS-485
3
For digital I/O
4
For Ethernet
Quantity
1
1
1
1
<Included Items>
• Owner's Manual
• Installation Manual
• Network Configuration Guide
1
• Data Analyzer
• Report Creation Software
• Section Changeover Software
4
Fixing screw (M4×12) for attaching the main unit from the front
4
Fixing screw (M3×8) for attaching the main unit from the rear
2
RS-485 cable crimp connector
2
For fixing the power adapter
1
For fixing the power adapter
Wire type / wire diameter / wire length
Microphone cord (shielded) (two-core) for instrumentation
2
1.25 mm
, up to 1000 m (total extension distance)
2
2.00 mm
, up to 2000 m (total extension distance)
Microphone cord (shielded) (two-core) for instrumentation
2
1.25 mm
, up to 500 m (total extension distance)
Two-core cable
2
0.3 mm
, up to 100 m
LAN cable (category 5 or above)
Maximum length: 100 m