[9-4 Maintenance LED Display and Troubleshooting ]
2. Collecting operation data
No.
Switch
Meaning
6
Collection in progress
7
Collection suspended
SW6-10:
OFF
SW4:
No.28
8
Flash memory error
9
HWE18240_GB
Maintenance LED Display
Error
Description
"ON" OC is collecting operation da-
ta. A blinking display indicates that
data collection is temporarily sus-
pended. No switch setting is neces-
sary. Data collection will be
resumed automatically. See Sec-
tion [9-4-2 Troubleshooting]2-(1).
"OFF" Collection of operation data
is suspended.
"F-Er" Collection of operation data
is suspended due to failure in the
flash memory used to store opera-
tion data. It may be necessary to
change the board. See Section [9-
4-2 Troubleshooting]2-(2).
"Err" Error was found due to the fail-
ure in units. After addressing the
cause, data collection needs to be
restated. See Section [9-4-2 Trou-
bleshooting]2- (3).
chapter 9 -
11