Error Code Definitions And Solutions: Codes [6000 - 6999]; Error Code [6201]; Error Code [6202] - Mitsubishi Electric PUHY-HP72 Service Handbook

Table of Contents

Advertisement

[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]

7-8

Error Code Definitions and Solutions: Codes [6000 - 6999]

7-8-1

Error Code [6201]

1. Error code definition
Remote controller board fault (nonvolatile memory error)
2. Error definition and error detection method
This error is detected when the data cannot be read out from the built-in nonvolatile memory on the remote controller.
3. Cause, check method and remedy
(1) Remote controller failure
Replace the remote controller.
7-8-2

Error Code [6202]

1. Error code definition
Remote controller board fault (clock IC error)
2. Error definition and error detection method
This error is detected when the built-in clock on the remote controller is not properly functioning.
3. Cause, check method and remedy
(1) Remote controller failure
Replace the remote controller.