VR9205R SERIES 1000 DIRECT IGNITION GAS CONTROL WITH INTEGRATED GAS/AIR MODULE
Wiring
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect the power supply before making wiring
connections. More than one disconnect may be
involved.
Follow the wiring instructions furnished by the appliance
manufacturer, if available, or use the general instructions
provided below. When these instructions differ from the
appliance manufacturer, follow the appliance
manufacturer instructions.
All wiring must comply with applicable electrical codes
and ordinances.
1. Disconnect power supply before making wiring con-
nections to prevent electrical shock or equipment
damage.
2. Check the power supply rating on the gas control
and make sure it matches the available supply.
Install a transformer and other controls as required.
3. Connect the control circuit to the gas control
terminals.
4. Ensure combustion chamber is free of gas before
startup.
5. Adjust thermostat heat anticipator to the rating
stamped on valve operator.
On-Off Switch
The on-off switch settings are as follows:
• OFF: Prevents main gas flow through the control.
• ON: Permits gas to flow into the control body. Under
control of the thermostat and direct ignition module,
gas can flow to the main burners.
Fig. 5. Proper use of wrench on gas control.
CAUTION
Equipment damage.
Can burn out valve coil terminals.
Never apply a jumper across (or short) the valve
coil terminals, even temporarily.
IMPORTANT
These gas controls are shipped with protective
seals over the inlet and outlet tappings. Do not
remove the seals until ready to install adapters
or connect the piping.

STARTUP AND CHECKOUT

On-Off Switch
The on-off switch settings are as follows:
• OFF: Prevents main gas flow through the control.
• ON: Permits gas to flow into the control body. Under
control of the thermostat and direct ignition module,
gas can flow to the main burners.
NOTE: Controls are shipped with the electronic on-off
switch in the ON position.
Perform Gas Leak Test
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury
or death.
Perform Gas Leak Test every time work is done on
a gas system.
IMPORTANT
Do not spray soap and water solution on the gas
control. Do not use an excessive amount of soap
and water solution to perform the gas leak test.
These can damage the control.