Structure Of A Modbus Telegram - JUMO LOGOSCREEN nt Interface Description

Paperless recorder with tft display, compactflash card and usb interfaces
Hide thumbs Also See for LOGOSCREEN nt:
Table of Contents

Advertisement

4.4 Structure of a Modbus telegram

Data structure
A minimum response time can be set in the controller under the
menu point Configuration
minimum waiting time before an answer is transmitted (0...500
ms). If a smaller value is set, then the response time may be longer
than the preset value (internal processing takes longer), the
controller answers as soon as internal processing is completed.
The preset time of 0 msec means that the controller responds at
the maximum possible speed.
The minimum response time, which can be set is required by the
RS485 interface in the master, to be able to switch over the
interface drivers from transmit to receive. This parameter is not
required for the RS232 interface.
t
The master has to observe this waiting time before starting a new
2
data request.
for RS232
for RS485
No data requests from the master are permitted during t
paperless recorder will either ignore the request or declare it to be invalid.
All telegrams have the same structure:
Slave address
1 byte
Each telegram contains four fields:
Slave address
device address of a specific paperless recorder
Function code
function selection (read, write words)
Data field
Contains information (according to the function code):
• Word address/bit address
• Number of words/bits
• word/bit values
Checksum
detection of transmission errors
4 Modbus protocol description
min. 3.5 times the transmission time
required for 1 character (the time
depends on the baud rate)
60ms
Function code
1 byte
Interface. This preset time is the
and t
1
Data field
Checksum
x byte
, because the
2
CRC16
2 byte
17