Mitsubishi SCM80ZA Manual page 58

Inverter multi-split system room air-conditioner [4 room] (air to air pump type)
Table of Contents

Advertisement

(2) Indication of self diagnosis
Indoor unit indicator
RUN lamp
TIMER lamp
1 time flash
Comes on
2 time flash
Comes on
5 time flash
Comes on
6 time flash
Comes on
Keeps flashing
1 time flash
Keeps flashing
2 time flash
Comes on
1 time flash
Comes on
2 time flash
Comes on
2 time flash
Comes on
3 time flash
Comes on
4 time flash
Comes on
5 time flash
Comes on
6 time flash
Notes (1) Ceiling recessed type only
(2) Wall mounted type only
(3) LED 5 will go out when even one unit is operating properly or there is an abnormality with the outdoor unit power supply. It will also go out during
normal operation.
108
Outdoor unit indicator
Description
of trouble
(LED5)
Indoor heat
Stays off
exchanger
thermistor error
Room temperature
Stays off
thermistor error
Drain
Stays off
abnormality
(1)
Indoor fan
Stays off
(2)
motor error
Outdoor
Stays off
temperature
thermistor error
Outdoor heat
exchanger gas
Stays off
pipe thermistor
error
1 time flash
Current cut
Trouble of
2 time flash
outdoor unit
On for 4 seconds
Discharge pipe
and off for 4
thermistor error
seconds
Over current
3 time flash
Over heat of
4 time flash
power transistor
Over heat of
5 time flash
compressor
Error of signal
6 time flash
(3)
transmission
Cause
When heat exchanger thermistor temperature
Broken heat exchanger
of –20 °C or under continued for more than
thermistor wire
3 seconds while operation is stopped. (This
Connector poor connection
is not displayed during operation.)
When room temperature thermistor temper-
Broken room temperature
ature of –20 °C or under continued for more
thermistor wire
than 3 seconds while operation is stopped.
(This is not displayed during operation.)
Connector poor connection
Drain at reverse gradient
Float switch motion
Float switch defective
When air conditioner is operating and indoor
fan motor is turned ON, indoor fan motor
Defective fan motor
speed of 400 rpm or under continued for
more than 30 seconds. (Air conditioner
Connector poor connection
stops.)
When outdoor temperature sensor temper-
Broken outdoor thermistor
ature of –40 °C or under continued for more
wire
than 3 seconds while operation is stopped.
(This is not displayed during operation.)
Poor connector connection
When heat exchanger entrance thermistor
Broken heat exchanger gas
temperature of –50 °C or under continued
pipe thermistor wire
for more than 3 seconds while operation is
stopped. (This is not displayed during oper-
Poor connector connection
ation.)
Compressor locking
When converter output current which ex-
Open phase on compressor
ceeds setting value is detected.
output
(Compressor stops.)
Shortcircuit on power
transformer
Broken power transformer
When the input current of 1 A or less is de-
Broken compressor wire
tected for 30 continuous seconds or more.
(Compressor stops.)
Compressor blockage
Broken discharge pipe
When the discharge pipe thermistor temper-
thermistor wire
ature measures an interrupted signal (less
than 7 °C) of 10 seconds or more.
Connector poor connection
When the input current value exceeds the set
Overload operation
value. (Compressor stops)
Overcharge
When power transistor temperature exceeds
setting value.
Cooling problem
(Compressor Stops.)
When discharge pipe thermistor value ex-
Gas shortage
ceeds setting value.
Defective discharge pipe
(Compressor Stops.)
thermistor
Defective power supply
If serial signal cannot be sent or received for
Broken signal wire
1 minute and 55 seconds continuously.
Defective indoor/outdoor
unit circuit boads
: http://splitoff.ru/tehn-doc.html