Mitsubishi SCM80ZA Manual page 52

Inverter multi-split system room air-conditioner [4 room] (air to air pump type)
Table of Contents

Advertisement

(c) Installation
12
Ceiling
15
(d) Installation procedure
Use the bolts (M8 × 2) to secure the sus-
1)
pension hardware so that it is 90 mm be-
low the ceiling surface.
2)
Use the band to tightly secure the flexible
duct (ø 150) to the air outlet chamber and
duct joint on the indoor unit itself so that
it will not come off and there will be es-
caping of air. Be sure to insulate this area
from the top with heat insulation in order
to prevent condensation.
3)
Use pan-head screws to secure the air out-
let panel to the air outlet chamber. At this
time, make sure there are no gaps between
the air outlet chamber and the air outlet
panel.
Note (1) If the outer covering of the flexible duct breaks, it
can be repaired with tape or other such material.
Escaping air could cause condensation.
102
357 (Suspension bolt pitch)
333
166.5
Round duct
connection port
10
377 (Ceiling opening dimension)
407
Suspension bolt (M8)
Flat washer (M8)
Flat washer (M8)
12
Suspension bolt M8 × 2
166.5
(Procured by customer)
Air outlet chamber
10
Air outlet panel
15
Nut (M8)
Nut (M8)
Flexible duct (ø 150)
Provide heat insulation
: http://splitoff.ru/tehn-doc.html
Unit: mm
83
91
45.5
45.5
52.5
52.5
15
105
15
(Ceiling opening dimension)
135
Air outlet chamber
Air outlet panel
Indoor unit