Mitsubishi SCM80ZA Manual page 27

Inverter multi-split system room air-conditioner [4 room] (air to air pump type)
Table of Contents

Advertisement

(b) SRRM model
When the timer is set to "ON" at the operation changeover is in the cooling or the heating mode, and in the cooling or the
heating mode at automatic operation, the pleasant reservation timer is actuated to start by the room temperature thermistor
(Th1) at 5 to 80 minutes before the set time irrespective of the time set by the timer.
Operation mode
Heating
Coolng
Notes (1) At 5 minutes before the timer ON time, operation starts regardless of the temperature of the room temperature thermistor (Th1).
(2) This function does not actuate when the operation select switch is set at the dehumidifying as well as the dehumidifying in the auto mode.
However, the operation of item (1) above is performed during the dehumidifying in the auto mode.
(3) During the pleasant reservation operation, both the operation lamp and timer lamp illuminate and the timer lamp goes off after expiration of the timer, ON setting
time.
(6) Cooling operation
(a) Summary
1) Capacity control
Capacity control is within the range shown above. If demand capacity of the indoor units exceeds the maximum capacity
of the outdoor unit, the demand capacity will be proportionally distributed.
2) Outdoor unit frequency control (30 ~ 104Hz)
The decision frequency is based on the total indoor demand frequency as follows:
Indoor demand frequency total
30 Hz or less
More than 30 Hz, but 104 Hz or less
More than 104 Hz
Note (1) The total indoor demand frequency is based on the value for each of the units shown in item (b).
(b) Mode switching
Within the selected mode, the unit operates using the values shown below which were obtained by multiplying a conversion
coefficient to the indoor unit demand frequency.
Model (Indoor)
Operation Mode
Automatic
High
Medium
Low
Hi power
Econo
Note (1) The values in parenthesis ( ) indicate SRRM40HENG-L.
(c) Operation of Major Functional Components in Cooling Mode
Operation
Functional
components
Demand frequency
Fixed
Indoor
unit fan
Automatic
Outdoor unit fan
Electronic
expansion valve
(EEVA, B, C, D)
Compressor
Operating start time (amount of time
Room. temp thermistor (Th1)
previous to set that operation begins)
Under 5˚C
Under 10˚C
Under 15˚C
Over 15˚C
Over 40˚C
Over 35˚C
Over 30˚C
Under 30˚C
Model
SCM80ZA
Capacity
1.8 ~ 8.6 kW
22
25
30
30
30
30
30
30
30
30
30
30
30
30
Thermostat OFF
Cooling
(All indoor units)
0
See preceding table
(All indoor units)
According to mode switching
According to demand frequency
According to mode switching
According to decision frequency
OFF
According to decision
According to stop mode
frequency
ON
OFF
80 mins.
30 mins.
15 mins.
5 mins.
80 mins.
30 mins.
15 mins.
5 mins.
Decision frequency
30 Hz
30 to 104 Hz
104 Hz
28
32
30 ~ 36
30 ~ 38
30 ~ 36
30 ~ 38
30
30
30
30
34
38
30
30
Thermostat OFF
Stop, abnormal stop
(Some of indoor units)
(Some of indoor units)
0
(Thermostat off units)
(Stop, abnormal stop units)
First speed or low
According to decision frequency
All closed
All closed
(Thermostat off units)
(Stop, abnormal stop units)
ON
: http://splitoff.ru/tehn-doc.html
40
50
30 ~ 44 (30 ~ 42)
30 ~ 54
30 ~ 48 (30 ~ 42)
30 ~ 54
30 ~ 40 (30)
30 ~ 36
30
30
44
54
30
30
Failure
(Outdoor Unit)
0
0
(All units)
OFF
OFF
OFF
According to stop mode
ON
OFF
77