(iii) Finishing conditions
When at least one of the hot stand-by cut conditions described below is met during the hot stand-by
function is activated, the hot stand-by function becomes inoperable.
1) When the hot stand-by function is activated during the above-mentioned condition which was
described in article 1 :
1 After 20 minutes elapsed since the power ON.
2 When the operation mode was changed from "STOP" to "COOLING" or "HEATING".
2) When the hot stand-by function is activated during the above-mentioned condition which was
described in article 2 :
1 When the outer air temperature thermister entered the OFF range.
2 When the operation mode was changed from "STOP" to "COOLING " or "HEATING".
(e) Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor blower is controlled based on the temperature of the
indoor unit heat exchanger (detected with Th2, indoor unit heat exchanger thermistor) to prevent blowing of cool wind.
SKM22, 25, 28, 32, 40 models
¡
Normal mode (Normal heating operation, operation after HI POWER completion)
Indoor blower
3rd speed
2nd speed
1st speed
Note (1) Refer to the table shown above right for the values a and b.
¡Hot keep M mode [During HI POWER operation (for 15 min.)]
Indoor blower
1st speed
Note (1) Refer to the table shown above right for the values a and b.
SKM50 model
¡Normal mode (Normal heating operation, operation after HI POWER completion)
Indoor blower
3rd speed
2nd speed
1st speed
OFF
a
b 27.5 28 29.5
Note (1) Refer to the table shown above right for the values a and b.
6th speed
5th speed
4th speed
Indoor heat exchanger temp. (˚C)
4th speed
3rd speed
2nd speed
Indoor heat exchanger temp. (˚C)
6th speed
5th speed
4th speed
31.5
34
Indoor heat exchanger temp. (˚C)
7th speed
7th speed
6th speed
5th speed
8th speed
7th speed
36
37.5
39
40
: http://splitoff.ru/tehn-doc.html
¡
Values of a, b
a
b
At 0 Hz command
22
25
Other than 0 Hz
17
19
command
¡
Values of a, b
a
b
At 0 Hz command
22
25
Other than 0 Hz
17
19
command