NOTE: It is important to exit PtP mode within the three minute time limit mentioned above. If you do not, none of the device
pairings will be remembered and you have to start the process over from the beginning.
Pairing a device to an existing network
If you need to add the LMPX-600 to an existing in room network, follow the procedure below:
1. Enter wireless Push-to-Pair (PtP) mode on the room controller. Press the Config button three times (within three seconds)
until the LED on the room controller flashes green.
2. Enter PtP mode on the LMPX-600. Press the Config button three times. As with the room controller, the LED on the sensor will
flash green.
3. Pair the devices. Press the Config button on the LMPX-600 once to pair the LMPX-600 to the room controller. The load
connected to the room controller will toggle once (if the load is OFF, it will turn ON; if ON, it will turn OFF) to indicate that pairing
was successful and its config LED will turn solid green.
4. Exit PtP mode. Exit PtP on the room controller, by pressing the Config button 3 times. The LED on the room controller will flash
blue while it completes the pairing process. The Network ID of the LMPX-600 will change to the value used by the previously
paired devices and the room controller also returns to that value.
DEVICE PAIRING AND UNIT ADJUSTMENT USING THE DLM CONFIG APP
The DLM Config App is available for both iOS
your device to download.
The app provides the ability to pair various devices in a room. Additionally, you can modify load
binding and edit various DLM parameters for each device.
For details on the features and operation, download the DLM Config App User Guide from the wattstopper web site at :
https://www.legrand.us/wattstopper.aspx
NOTE: LMCS-100 software, version 4.7 or later can also be used to pair devices and edit DLM parameters. However, LMCS-100
requires use of an LMBR-650.
When you reset the LMPX-600, the Channel and Network ID will return to their default values, and if the
sensor was previously paired, it will no longer be connected to that room network. All DLM parameters are
also returned to their default values.
There are two ways to reset the LMPX-600:
• Press the Config button 10 times. The LED will blink green each time the Config button is pressed
(except for the 7th press which will blink blue). After the 10th press, the LED will turn red then briefly
turn white indicating it is rebooting.
• On the back of the sensor, is a small hole that will fit a paper clip. Use a paper clip to depress the
button inside that hole and hold for 10 seconds. When you first press the reset button, the LED will
blink red once, then after the 10 seconds will reboot and the LED will briefly turn white, indicating it is
rebooting.
®
and Android devices
®
. Search "DLM Config" on
RESETTING THE LMPX-600
5
Paper Clip
Reset Hole