Master controlled Variable Speed Drives (VSD)
The PROFIBUS Field-bus was designed to give you
unprecedented flexibility and command over your
VSD controlled system. The PROFIBUS will perform
as an integrated part of your VLT VSD, giving you
access to all parameters relevant to your application.
The VSD will always act as a slave, and together with
a master it can exchange a multitude of information
and commands. Control signals such as speed
reference, start / stop of motor, reverse operation,
etc. are transmitted from the master in the form of a
telegramme. The VSD acknowledges receipt by
transmitting status signals, such as running, on
reference, motor stopped and so on to the master.
The VSD may also transmit fault indications, alarms
and warnings to the master, such as Overcurrent or
Phaseloss.
The PROFIBUS communicates according to the
PROFIBUS Protocol Standard DIN 19245 parts 1 and
3. This means that it can communicate with all
masters that comply with this standard, but it does
not necessarily mean that all services available in the
PROFIBUS standard are supported. The VDI / VDE
3689 PROFIBUS Profile for Variable Speed Drives is a
subset of PROFIBUS which only supports the
services relevant to speed control applications.
PROFIDRIVE is an implementation of VDI / VDE 3689
profile created by DANFOSS and a number of other
companies.
Cable lengths/number of nodes
The maximum cable length in one segment is
depending on the transmission speed. The total cable
length includes drop cables if any. A drop cable is the
connection from the main bus cable to each node if a
T-connection is used instead of connecting the main
bus cable directly to the nodes, see drop cable
length. The table below shows the maximum allowed
cable length and maximum number of nodes/VLT's
with 1, 2, 3 and 4 bus segments.
Max. total bus cable lenght
1 segment:
32 nodes
Transmission
(31 VLT)
speed
[m]
9.6-187.5 kBaud
1000
500 kBaud
400
1.5 MBaud
200
3 MBaud
100
MG.90.A2.02 – VLT is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
Communication partners
In a control system the VSD will always act as a slave,
and as such it may communicate with a single master
or multiple masters depending on the nature of the
application. A master may be a PLC or a PC that is
equipped with a PROFIBUS communication card.
Physical layer
The field of application of a field-bus system is
primarily determined by the transmission media and
the physical bus interface selected. The type of bus
cable required for the application and its installation
(physical layer) are particularly important factors, in
addition to the required transmission reliability of the
physical level.
Though a fundamental feature of the PROFIBUS stan-
dard is the possibility of specifying several different
physical interfaces, the standard, at the time of
printing, has allowed for one universal specification
only, namely the EIA Standard RS 485-A, which has
found acceptance both in the field of factory automa-
tion and in several areas of the processing industry.
Note that a repeater is a node in both of the two
segments it connects. The number of VLT is based on
a single master system. If there are more masters the
number of VLT must be reduced correspondingly.
2 segments:
3 segments:
64 nodes
96 nodes
(1 repeater, 61 VLT)
(2 repeaters, 91 VLT)
[m]
[m]
2000
3000
800
1200
400
600
200
300
4 segments:
128 nodes
(3 repeaters, 121 VLT)
[m]
4000
1600
800
400
5