953 Warning parameter 1 (WARN. PARA)
Selections:
Read only
Function:
A 16 bit bitstring where each bit is associated with a
specific warning according to the list below.
Bit
Bit = "1" when:
0
LSB
Connection with DP-master is not ok
1
Not used
2
FDL (Field-bus Data link Layer) is not ok
3
Clear data command received
4
Actual value is not updated
5
Spontaneous message FIFO overflow
6
PROFIBUS ASIC is not transmitting
7
Initialising of PROFIBUS option is not ok
8
Not used
9
Not used
10
Not used
11
Not used
12
Fatal DPR-handling error/Error code
during init.: Bit 0
13
Fatal DPR-handling error/Error code
during init.: Bit 1
14
Fatal DPR-handling error/Error code
during init.: Bit 2
15
MSB
Fatal DPR-handling error/Error code
during init.: Bit 3
Explanation of err
Explanation of err
Explanation of err
Explanation of err
Explanation of error codes:
or codes:
or codes:
or codes:
or codes:
If init. went wrong (bit 7 asserted) following codes are
defined:
Code
0
OK
1
Init. channel not empty
2
No resp. on command „Init SPC3 controller"
3
No resp. on command „No action"
4
No resp. on writing init.-data
5
No valid resp. on writing init.-data
6
No positive resp. on writing init.-data
MG.90.A2.02 – VLT is a registered Danfoss trademark
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
If errors occur during DPR-handling (bit 7 not
asserted)
Code
0 OK
1 Fatal error in warning channel
2 Fatal error in spontaneous channel
3 Fatal error in channel for input of process data
4 Fatal error in channel for output of process data
5 Fatal error in parameter channel 1
6 Fatal error in parameter channel 2
7 Fatal error in parameter channel 3
15 Fatal error in DPR form SPC3
967 Control word
Selections:
16 bits binary code
See page 22.
968 Status word
Selections:
Read only
See page 22.