970 Edit set up selection (EDIT SETUP SELECT)
Selections:
Factory setup
(FACTORY SETUP)
Setup 1
(SETUP 1)
Setup 2
(SETUP 2)
Active setup
(ACTIVE SETUP)
Function:
As parameter 005, described in the FCM 300 design
guide (MG.03.Bx.02) and the VLT 2800 design guide
(MG.28.Ex.02).
971 Store data values (STORE DATA VALUE)
Selections:
No action
(NO ACTION)
Store active setup (STORE ACTIVE SETUP)
Store edit setup
(STORE EDIT SETUP)
Store all setups
(STORE ALL SETUPS)
Function:
Parameter values changed via PROFIBUS is only
stored in RAM meaning that the changes are lost at
power down. This parameter is used to activate a
function that stores all parameter values in the
EEPROM thus retaining changed parameter values at
power down.
Description of selections:
No action: The store function is inactive.
Store active setup: All parameter values in the active
setup will be stored in the EEPROM. The value
returns to No action when all parameter values have
been stored.
Store edit setup: All parameter values in the setup
you are editing will be stored in the EEPROM. The
value returns to No action when all parameter values
have been stored.
Store all setups: All parameter values in both setups
will be stored in the EEPROM. The value returns to
No action when all parameter values have been
stored.
Factory setting
34
FCM 300 PROFIBUS / VLT 2800 PROFIBUS
980-982 Defined parameters (DEFINED PNU'S)
Selections:
[0]
Read only
[1]
[2]
Function:
[5]
The three parameters hold a list of all the parameters
that are defined in the FC motor / VLT 2800. It is
possible to read single elements of the list by DP by
using the corresponding subindex. The subindexes
start at 1 and follow the order of the parameter
numbers.
Each parameter holds up to 116 elements (parameter
numbers).
[0]
[1]
When a 0 is returned as parameter number the list
[2]
ends.
[3]
990-992 Modified parameters
(MODIFIED PNU'S)
Selections:
Read only
Function:
The three parameters hold a list of all the FC motor /
VLT 2800 parameters that have been changed from
factory setting. It is possible to read single elements
of the list by DP by using the corresponding subindex.
The subindexes start at 1 and follow the order of the
parameter numbers. Each parameter holds up to 116
elements (parameter numbers). The number of
parameters (990, 991 and 992) in use depends on
how many parameters have been changed from
factory setting.
Read only parameters, as for example data read out
parameters, will not be registered as modified
eventhough they are changing.
When a 0 is returned as parameter number the list
ends.