Samsung AG026MN1DEH/EU Service Manual page 55

Fan coil unit
Hide thumbs Also See for AG026MN1DEH/EU:
Table of Contents

Advertisement

Option
SEG19
Individual control
Explanation
Page
with remote control
Indication Details Indication Details Indication
Indication
and
details
3
*1) Minimal Fan operation during Thermo Off
(
‑ Fan will run for 20 seconds every 5 minutes during heating Thermo off
‑ Fan will stop or run at ultra‑low speed depending on settings during cooling Thermo off
(*2) 1: Fan will always be On if hot water heater is On
3: Fan will be Off if hot water heater in cooling‑only indoor unit is On
[In order to use the applicable option function, a cooling and heating converter (ACM‑C200) must be installed in the outdoor unit and
fixed to cooling mode]
(*3) If 2, 3 is selected to use as external heater On/Off signal, the external contact point control Monitoring signal will not be
outputted.
2: Fan will always be On when external heater is On
3: Fan will be Off when external heater is On in the cooling‑only fan coil unit
[In order to use the applicable option function, a cooling and heating converter (ACM‑C200) must be installed in the outdoor unit and
fixed to cooling mode]
※ If set as SEG9=3 or SEG15=3 to set Fan Off regarding the cooling‑only fan coil unit, the external sensor or cable remote control
sensor must be used to accurately detect
(*4) Output will be generated when running cooling or dehumidifying mode
(*5) An Economizer control is required to set outside air introduction cooling
(*6) Initial setting value
‑ 4‑Way cassette, compact 4‑Way cassette: 5 ℃
‑ Other fan coil units: 2 ℃
(*7) This function only applies to the 4‑Way cassette and compact 4‑Way cassette. If the outdoor unit switches to heating operation
right after cooling is finished, the condensate water remaining in the Drain Pan will evaporate due to the heat of the fan coil unit heat
exchanger. This may then condense on the surface of the product and drip into the living space. If using the applicable option, after
the outdoor unit switches from cooling to heating, run the Fan (for maximum 20 minutes) even if the relevant fan coil unit is turned
off so that the steam will be discharged outside the unit.
SEG20
Heating installation compensation Offset / Removing
condensate water in the Heat mode
Heating
installation
compensation
0
Default (*6)
Channel
0 or 1
1
1
2
Channel
2
3
Default (*6)
2
Channel
3
4
3
Channel
4
5
54
indoor temperature.
SEG21
Details
Removing condensate water in
the Heat mode
Offset
Disuse
2 ℃
Disuse
5 ℃
Disuse
Use (*7)
2 ℃
Use (*7)
5 ℃
Use (*7)
4-13
Trouble shooting
SEG22
SEG23
Human
Human control
control
Indication
Details
0
Disuse
Turn OFF if absent
1
for 30 minutes
Turn OFF if absent
2
for 60 minutes
Turn OFF if absent
3
for 120 minutes
Turn OFF if absent
4
for 180 minutes
Turn OFF if absent
5
for 30 minutes and
advanced function (*1)
Turn OFF if absent
6
for 60 minutes and
advanced function (*1)
Turn OFF if absent
7
for 120 minutes and
advanced function (*1)
Turn OFF if absent
8
for 180 minutes and
advanced function (*1)