4-1-4. Fan Coil Unit Installation Option Setting (setting option to suit installation site conditions)

1. Check whether or not power is being supplied to the fan coil unit.
▶ If power is not being supplied, a separate power supply device will be required.
2. A panel or DISPLAY that can receive option inputs must be connected to the fan coil unit.
3. Depending on the air‑con installation conditions, the fan coil unit installation options must be set.
▶ The initial setting value of the installation options of the fan coil unit is "020010‑100000‑200000‑300000".
▶ The individual control setting (SEG20) of the fan coil unit is a setting to individually control the fan coil unit when more than 1 fan coil units are
installed.
4. Set the fan coil unit options using the remote controller.
■ 02 series installation option
SEG1
0
SEG7
1
SEG13
2
External control
SEG19
Remote control individual
3
▶ 1 WAY/2WAY/4WAY/360 cassette model:
‑ It will be set as "Use + 3 minute delay" even if the drain pump (SEG8) setting value is set as "0".
‑ If the SEG18 setting value is designated a number other than 2 or 6, the filter usage time (SEG18) will automatically be set as 1000
hours.
▶ If set as a value other than the SEG setting, it will be set as the default "0".
▶ The SEG5 central control usage option is set to the default 2 (Use). Therefore, using the central control does not require a separate
setting.
At this point, an error will not occur even if central control is not connected, and change it to 0 (Disuse) if the fan coil unit will be
excluded.
▶ The output of the external Heater of SEG15 will be outputted through an AIM‑B14 connection (please refer to AIM‑B14 manual).
SEG2
SEG3
2
Robot cleaning
SEG8
SEG9
Drain pump
Hot water heater
SEG14
SEG15
External control output
SEG20
SEG21
Heating setting
control
compensation
SEG4
External temperature
sensor
SEG10
Electronic heater
SEG16
S‑Plasma ion
SEG22
4-11
Trouble shooting
Fan coil unit
1(L)
2(N)
SEG5
SEG6
Central control
FAN RPM compensation
SEG11
SEG12
Master / Slave
SEG17
SEG18
Buzzer
Filter usage time setting
SEG23
SEG24
Human sensor
F2
F1