INSTALLATION INSTRUCTIONS
Gas Conversion Kits
Use with Valor 2100PKN/PKP, 2200KN/KP, 2200LKN/LKP, and 2200RKN/RKP heaters ONLY
This appliance is certifi ed for use from 0–4,500 feet. For
altitudes above 4,500 feet, see local codes.
Kit Contents
• 1 Pilot injector
• 1 Main burner injector
• 1 Set of conversion labels
• 1 bypass screw
Tools Required
• Wrenches, to disconnect gas line
• Small (jewelers size) fl at blade screwdriver, to set pres-
sure
• Small fl at blade screwdriver, to release pressure tap
on valve
• Needle nose pliers, to remove by-pass screw
• Hex (Allen) wrench, 4 mm or 5/32", to remove pilot injec-
tor
• Manometer, to set manifold pressure at the valve
• Appliance's installation manual
Specifi cations
Model
Gas
Altitude (Ft.)
Input Maximum (Btu/h)
Input Minimum (Btu/h)
Manifold Pressure (in w.c.)
Minimum Supply Pressure (in w.c.)
Maximum Supply Pressure (in w.c.)
Main Burner Injector Marking
Pilot Injector Marking
Min. Rate By-Pass Screw
General notes regarding conversion
We recommend that the gas conversion be done before the appliance is inserted in fi nal position into the cavity,
although it may be done after. The gas must be connected in order to set the manifold pressure.
4007021-02
© Copyright Miles Industries Ltd., 2019
LX Series
LX1 (2100NGK / 2100PGK)
LX2 (2200XNGK / 2200XPGK)
2100PKN 2100PKP
Natural
Propane
0-4,500 feet
25,000
25,000
14,000
14,000
3.5"
10"
5"
11"
10"
14"
DMS#42
DMS#53
51
30
185
125
 WARNING
This conversion kit shall be installed by
a qualified service agency in accordance
with the manufacturer's instructions and
all applicable codes and requirements
of the authority having jurisdiction. If
the information in these instructions is
not followed exactly, a fire, explosion
or production of carbon monoxide may
result causing property damage, personal
injury or loss of life. The qualified service
agency is responsible for the proper
installation of this kit. The installation
is not proper and complete until the
operation of the converted appliance is
checked as specified in the manufacturer's
instructions supplied with the kit.
Use this manual in conjunction with the
installation manual supplied with the
appliance.
2200KN
2200KP
2200LNK
2200LKP
2200RKN
2200RKP
Natural
Propane
36,000
36,000
19,000
21,000
4.0"
9.5"
5"
11"
10"
14"
DMS#32
DMS#49
51
30
220
160

Advertisement

loading

Summary of Contents for Valor LX Series

  • Page 1 LX1 (2100NGK / 2100PGK) Gas Conversion Kits LX2 (2200XNGK / 2200XPGK) Use with Valor 2100PKN/PKP, 2200KN/KP, 2200LKN/LKP, and 2200RKN/RKP heaters ONLY This appliance is certifi ed for use from 0–4,500 feet. For  WARNING altitudes above 4,500 feet, see local codes.
  • Page 2: Prepare The Appliance

    Prepare the appliance 5. R emove the burner (4 screws on LX1, 6 screws on LX2). 1. Remove the barrier, sill, and front window—see ap- Very carefully slide to the right and lift the burner pliance’s Installation Manual. off . Be careful not to damage the pilot head.
  • Page 3 Remove and replace the minimum rate 2. Remove the injector. bypass screw minimum rate bypass You can access the bypass screw location screw on the valve through the access hatch in the front panel of the appliance. Remove and replace the mini- mum rate bypass screw from the valve with the appropriately labelled bypass screw—see...
  • Page 4: Adjust The Air Shutter

    Because our policy is one of constant development and improvement, details may vary slightly from those given in this publication. Designed and Manufactured by / for Miles Industries Ltd. 190 – 2255 Dollarton Highway, North Vancouver, B.C., CANADA V7H 3B1 Tel. 604-984-3496 Fax 604-984-0246 www.valorfi replaces.com...
  • Page 5: Directives D'installation

    LX1 (2100NGK / 2100PGK) conversion de gaz LX2 (2200XNGK / 2200XPGK) Pour les foyers Valor 2100PKN/PKP, 2200KN/KP, 2200LKN/LKP et 2200RKN/RKP SEULEMENT Cet appareil est certifi é pour utilisation de 0 à 4 500 pieds.  AVERTISSEMENT Pour altitudes supérieures à 4 500 pieds, consultez la Ce kit de conversion doit être installé...
  • Page 6 Préparez l’appareil 5. Enlevez le brûleur (LX1 : 4 vis; LX2 : 6 vis) . Avec précautions, tirez le brûleur vers la droite puis 1. Enlevez le pare-étincelles, le seuil de fenêtre et la soulevez-le. Faites attention de ne pas endomma- fenêtre du côté...
  • Page 7 2. Enlevez l’injecteur. Indices signalétiques à la page 5. La vis est maintenue en place par un joint torique de caoutchouc. Il peut être nécessaire de devoir forcer le joint hors de sa position ou d’enlever la vis avec des pinces à bec effi lé. Réinstallez le brûleur et les plateaux du lit d’alimentation 1.
  • Page 8 4. Réglez la vis d’ajustement de pression sur la sou- 2. Réglez l’obturateur utilisant un tounevis pour bouger pape à l’aide d’un petit tournevis à lame—tel le levier vers la droite ou la gauche. qu’indiqué ci-dessous—alors que l’appareil fonc- tionne à plein régime pour produire la pression Set air shutter d’admission indiquée au tableau Indices signalétiques with a screwdriver...

This manual is also suitable for:

Lx1 2100ngkLx2 2200xngkLx2 2200xpgkLx1 2100pgk