Certification
6.2 EMC and Environmental Type Tests
Test
IEEE 1613.1/
IEC 61000-4-10
Environmental Type Tests
Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
IEC 60068-78
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3
IEC 60068-1-14
56
Description
Damped Oscillat-
ing Magnetic Field
Description
Cold Temperature
Cold Storage
Dry Heat
Dry Heat Storage
Humidity (Damp Heat, Steady State)
Vibration
Shock
Seismic
Change of Temperature
Enclosure Ports
Test Ad
Test Ab
Test Bd
Test Bb
Test Db
Test Levels
100 A/m for 1 s (100 kHz and 1 MHz)
Test Levels
-40 °C (-40 °F), 16 Hours
-40 °C (-40 °F), 16 hours
85 °C (185 °F), 16 Hours
85 °C (185 °F), 16 hours
95% (Non-Condensing),
55 °C (131 °F), 6 cycles
10 days @ 55 °C (131 °F)
and 93% Relative Humidity
2 g @ 10-150 Hz
30 g @ 11 ms
Method A, Class 2
5 Cycles (-40 to 85 °C or -40 to 185 °F)
Installation Manual, 09/2019, C79000-G8976-1103-13