2.7 Connecting Power
1
2
3
Figure 2.9
2.7

Connecting Power

The RUGGEDCOM RX1400 supports a single integrated high AC/DC or low DC power
supply.
NOTICE
Before installing the device, note the following:
2.7.1

Connecting High AC/DC Power

To connect a high AC/DC power supply to the device, do the following:
Electrical hazard – risk of damage to equipment.
Do not connect AC power cables to terminals for DC power. Damage to the power
supply may occur.
22
1
2
3
Normally Closed
Common
Normally Open
Failsafe Alarm Relay Wiring
An appropriately rated AC or DC circuit breaker must be installed.
Use minimum #16 gage copper wiring when connecting terminal blocks.
Equipment must be installed according to applicable local wiring codes and
standards.
CAUTION
RUGGEDCOM RX1400
Installation Manual, 09/2019, C79000-G8976-1103-13