Gira DALI 5422 00 Operating Instructions Manual page 4

Wireless control unit, 1-gang mini
Table of Contents

Advertisement

Wireless DALI control unit, 1-gang Mini
The connected DALI subscribers may be operated on different phase conductors.
The control cable and load cable can be run in a shared cable, e.g. NYM J 5×1.5.
Ensure that the control cable with regards type, cross-section and routing complies with
the VDE specifications for 250 V cables, DALI interface has basic insulation.
Connect control unit (5) and DALI ballasts (6) as shown in the connection example
(Figure 2). At the same time, note the information given by the manufacturers of the bal-
lasts.
In the case of more than 12 DALI subscribers, up to five additional control units can be
connected. When doing so, ensure correct polarity.
If multiple circuit breakers supply dangerous voltages to the device or load, couple the
miniature circuit breakers or label them with a warning, to ensure disconnection is guaran-
teed.
Insert the control unit into the appliance box in such a way that the Prog button (2) and
status-LED (3) are visible.
Switch position
PC
DALI
min.
*)
If the operating mode switch is turned from the position PC, the operating mode and
parameters are set to the default setting. The settings made with the eNet Server will
be lost.
Set the operating mode switch (1).
Switch on mains voltage.
The ballasts can be switched by briefly pressing the Prog button.
Status-LED (3) lights up: switched on
Status LED (3) off: switched off
32580922
10864978
Figure 2: Connection example
Figure 3: Operating mode switch
Function
Operating mode, parameter set with eNet
server *)
DALI mode
Setting of the minimum brightness
22.08.2019