Wireless DALI control unit, 1-gang Mini
Parameters
Extended channel settings
Parameters
Operating mode
Manual commissioning
Local Operation
Behaviour on voltage return
Brightness on voltage return
Behaviour after the end of the
disabling function
Manual saving of the scene
values
Switch-off warning
32580922
10864978
Setting options, Basic setting
Setting options, Basic setting
Normal operation
Continuous on
Continuous off
Basic setting: Normal Opera-
tion
On, Off
Basic setting: On
On, Off
Basic setting: On
On
Off
Last value
Configured brightness
Basic setting: Off
0...100 %
Basic setting: 100 %
On
Off
no change
Last value
Basic setting: No change
On, Off
Basic setting: On
On, Off
Basic setting: Off
22.08.2019
Explanations
reset the counter to "0". The
device must be programmed
to apply the change.
Explanations
see Device and channels
Blocks manual commissioning
for the device channel.
Note: In the "Off" setting, the
device cannot be reset to the
factory setting.
Blocks the output for operation
using the Prog button.
Defines the behaviour of the
output after voltage return.
Brightness value, set by the
output after voltage return
(mains voltage). The para-
meter "Behaviour after voltage
return" must be set to "Con-
figured position".
Note: If the value is above the
set maximum brightness or
below the minimum bright-
ness, then the system will
switch to the appropriate limit
value.
Behaviour of the output when
a block is removed.
Disables the saving of the cur-
rent brightness value as scene
value in an actuator for a com-
mand via a transmitter.
If the switch-off warning is act-
ive, then, during switch-off, the
system dims to minimum
brightness within 30 seconds
and only then switches off. If
the parameter "Dim down
ramp" is configured as longer
than 30 s, then the length of
10 / 14