SIMOLINK Pulse Generator
NOTICE
CAUTION
Siemens AG
GWE-477 764 4070.76 J
SIMOVERT MASTERDRIVES
02.2001
The SIMOLINK Pulse Generator can be switched over to the other
mode "100 kHz signal" through insertion of a jumper between
connector pin "SEL_100kHz" and GND.
Pin
Designation
2
A+
7
A–
4
B+
9
B–
1
SEL_100 kHz
3, 8
GND
5, 6
n.c.
Housing
Outer shield
9-pin SUB D socket with screw locking mechanism (UNC)
Table 5-3
Assignment of connector X2 for 100 kHz signal mode
To maintain immunity to interference, a shielded cable must be used
and the shield attached in the connector housing.
One or several drives/devices can be connected to the SLP module.
When the SLP is operated in conjunction with one drive/device, the
GND signal should be connected in the cable. If several drives/devices
are connected to the SLP, the GND signal should not be connected; it
must be noted in this respect that large deviations in the 0 V (GND) on
different drives/devices can cause disturbances or malfunctions on the
RS422 bus.
Operating Instructions
Meaning for 100 kHz signal
Track A 100 kHz not inverted
Track A 100 kHz inverted
Sign
not inverted
Sign
inverted
Selection of 100 kHz signal
Ground (see below)
Unused
Connections
Range
RS422
standard
RS422
standard
Insert
jumper to
GND!
5-3