9.3.

System

Issue
Cord plugged into intermittent or
switched off power source.
Water softener
Disconnected/faulty meter cable.
fails to regenerate
Defective power cord.
automatically.
Defective controller, meter or sensor. Replace or repair.
Bad programming.
Regeneration at
Controller improperly set, due to
wrong time.
power failure.
Improper regeneration.
Hard water
External bypass valve leaking.
leakage after
O-ring around riser pipe damaged.
regeneration.
Incorrect controller settings.
Meter blocked.
Meter cable defective.
System
regenerate always
Incorrect controller settings.
with 100% salt
setting (possible
variable refill
Water consumption depleted unit
malfunction).
capacity.
No conditioned
No brine in brine tank.
water after
Injector plugged.
regeneration.
Bypass valve in bypass.
No water flow
Meter probe disconnected or not fully
display on
connected to meter housing.
controller while
water is currently
Restricted meter turbine rotation due
being used.
to foreign matter in meter.
Ref. MKT-IM-038 / C - 15.11.2019
Cause
Installer Manual Foleo - Troubleshooting
Reset and recovery
Connect to constant power source.
Reconnect/replace cable.
Replace cord.
Program correctly.
Update time of day and day of week
programming.
Control brine dosage setting and
repeat regeneration.
Repair/replace bypass.
Replace o-ring.
Check that controller setting match
with your actual softener model.
Clean or change meter.
Change meter cable.
Check that controller setting match
with your actual softener model.
Reset and recovery. Check water
consumption in diagnostic mode. If
registered water consumption match
with unit capacity, this is then a normal
behaviour. If not, contact your supplier,
Add brine to brine tank.
Clean injector and screen.
Shift bypass valve to non-bypass
position.
Fully insert probe into meter housing.
Remove meter housing, free up
turbine and flush with clean water.
Turbine should spin freely. If not,
replace meter.
97 / 112